Thursday, April 23, 2009

Comm 10 Clarification

Several questions have been posed relating to the overfill requirements on USTs. The Comm 10 Spill and overfill prevention requirement applies as below:
Heating oil tanks (Comm 10.310 (5)) refers to Comm 10.505 for USTs 4,000 gallons or greater. Comm 10.310 (3) requires overfill prevention for heating fuel tanks less than 4K, but via other methods.


Comm 10. 350 Hazardous substance tanks overfill prevention is not addressed due to the specific compatibility issues and hazardous substance properties and characteristics.
Comm 10.505 applies to USTs that take delivery via a tight connect with the delivery hose. This applies regardless of the tank being "12,000 gallons, but being filled no more than 50% of capacity."

For USTs that routinely take delivery by hand-held nozzle and the fill pipe is not equipped with a tight connect fitting auto-shut-off is not required. Maintaining a tight connection with a hand-held nozzle poses a challenge, even with the gasket collar, and in many situations where a drop is via a "hand held nozzle, if the tank had a flapper type auto shut-off, when the shut-off activates it would produce a safety concern from blow back at the person fuelling and the surrounding area.

PEI RP 100-05-7.3.2 includes the following: "Shut-off devices that are designed for use with underground tanks should only be used with gravity deliveries and where there are liquid-tight connections between the delivery hose and the fill pipe."

Sheldon Schall, Chief
Storage Tank Regulation Section
Wisconsin Department of Commerce

US Mail: PO Box 7837, Madison, WI 53707-7837
UPS/FedEx: 201 W. Washington Ave., Madison, WI 53703
(608) 266-0956Fax: (608) 261-7725
Web site: http://commerce.wi.gov/

Thursday, October 16, 2008

New Comm 10 Adopted





The web page for the proposed (and newly adopted) revisions can be found here:

http://www.commerce.state.wi.us/er/ER-BST-Comm10CodeRevisionPage.html

Comm 10 has been adopted and the anticipated effective date is Feb 1, 2009. We are receiving inquiries regarding the ability to use the revised code now. Because the revised Comm 10 has formally been adopted (with an effective date of Feb 1st.) it is acceptable to use the revised Comm 10 for plan development and submittal if it is used entirely, including the respective adopted standards. A person cannot pick and choose between the current Comm 10 and the adopted Comm 10. If using the adopted revised code the submitter should attach a note that the plan submittal is developed in accordance with the revised version of the Comm 10 code.

Revised operator recordkeeping and system test requirements that may change under the revised code are not effective until February 1, 2009.

Sheldon Schall, Chief
Storage Tank Regulation Section
Wisconsin Department of Commerce
US Mail: PO Box 7837, Madison, WI 53707-7837
UPS/FedEx: 201 W. Washington Ave., Madison, WI 53703
(608) 266-0956
Fax: (608) 261-7725
Web site: http://commerce.wi.gov/

Contact information


Office of Safety and Loss Prevention
University of Wisconsin System Administration
(608) 262-4792
 
Clicky Web Analytics